Power loss within dive control

  • Safety Flash
  • Published on 11 August 2017
  • Generated on 5 September 2026
  • IMCA SF 20/17
  • 3 minute read

What happened?

During diving operations, there was a power loss scenario within dive control whereby both circuit breakers after the uninterruptible power supply (UPS) tripped, causing a loss of power to the electronic components of the dive system. Power was re-established using the UPS bypass switch. The dive was aborted to carry out investigation. No-one was harmed.

What went wrong? What were the causes?

During setup of the dive system the UPS was set to work on approx. 220VAC input (the input from a vessel generator power supply typically fluctuates). The UPS was also set up on the assumption that the power from the vessel would not drop below 85% of the expected supply voltage (a drop to 187VAC).

Investigation confirmed that this is in fact what happened – the supply voltage did indeed drop below the minimum threshold of 187VAC. When this happened, an automatic and internal bypass in the UPS kicked in to keep power supplied to the outlet side. Therefore, the low voltage was transferred through the internal UPS bypass and into the circuit breakers that protected all the electronic equipment in dive control.

When attached to a fixed output load (such as electronic equipment), a voltage drop will necessarily cause an increase in current flow. The current increased to the point where the circuit breakers tripped to further protect the electronic equipment. This disconnection of the power to the electronics shut them down without the UPS taking over or giving any sort of alarm condition.

This voltage drop may have been gradual and therefore was not noticed. It wouldn’t have affected any other circuit breakers as there wouldn’t have been any power spike. However, since the UPS corrects to 85% of the input voltage, once that limit was reached it automatically transferred to the bypass, thereby immediately causing a power spike on the output side as the voltage changed from 220VAC (UPS corrected) output to <187VAC (UPS bypassed output).

Further investigation revealed that the low voltage was a result of a large current draw, in turn as a result of other equipment on the same power bus being used at the same time. In this case, it was discovered that the ROV was being recovered from the water at the time of the power loss. On this vessel, the dive system power is taken from the same power bus as that which is used for the ROV.

What actions were taken? What lessons were learned?

  • Immediate Action: Verify that the ROV BUS tie breaker on the vessel 440VAC power distribution panel was in the open position. This circuit breaker needs to remain in the open positon at all times during diving and chamber operations.

  • Set the UPS on all similar vessels to prohibit the use of the internal bypass again. This means that if at any point a low voltage scenario occurs again, the UPS will switch onto the battery backup, give an audible alarm and the internal bypass will never be used.

  • The dive supervisors should be made aware that this alarm may occur at any time a high draw/low voltage situation is experienced again and all they need to do is to call the dive techs to confirm the UPS status.

  • A daily “health” check of the UPS system has been added to the planned maintenance system for all company UPS systems.

  • Due to the nature of the issue, the manufacturer was contacted during the investigation to seek advice on the UPS. The manufacturer had not reported similar occurrences, but a report will be sent to them for their records.

Latest Safety Flashes:

GPS jamming and spoofing – good practice example

A Member’s vessel in the Red Sea encountered GPS jamming.

Read more
LTI – Shoulder strain when crew member was descending the stairs

A crew member sustained an injury to their shoulder as they were descending a flight of stairs into an ROV hangar.

Read more
Emergency escape hatch found blocked

Emergency escape hatch to the deck could not be opened.

Read more
Crew member sustained hand injury during lifting operations

A crew member sustained a hand injury during a lifting operation involving a main engine cylinder head.

Read more
NOPSEMA: Lifting operations dangerous occurrences and injuries

NOPSEMA has published a safety bulletin relating to lifting operations in the offshore industry.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.