Near miss: Fire hazard from engine room equipment failure
- Safety Flash
- Published on 21 March 2017
- Generated on 14 September 2026
- IMCA SF 06/17
- 3 minute read
Jump to:
A member has reported a near miss incident relating to a fire hazard in a separator room.
What happened?
During routine planned maintenance and testing of a main engine lube oil purifier during a port call, smoke was noted emerging from beneath the guard of the purifier pre-heater.
The vessel’s smoke detection system activated, indicating smoke in the separator room. A General Alarm was sounded and a broadcast made to inform the crew that a potential emergency was developing and “In Port” fire procedures were activated.
The heater was immediately isolated both electrically and mechanically. Bridge was informed that although smoke was present there was no fire and the situation was under control. The heater was monitored to ensure that it cooled appropriately and presented no further danger.
safety cut-off removed for investigation; the failed Reset button is highlighted
Findings
Our Member noted the following:
- There was some initial confusion at the time of the alarm, for two reasons:
-
- The vessel was preparing to conduct an “At Sea” emergency drill, which required personnel to muster on board, rather than ashore, and personnel assumed the drill had been brought forward.
- Communications were hampered by a fault with the vessel PA system. The Master had to rely on portable UHF communications to clarify the exact situation.
- The vessel was preparing to conduct an “At Sea” emergency drill, which required personnel to muster on board, rather than ashore, and personnel assumed the drill had been brought forward.
What caused the incident?
- The immediate cause was the overheating of the lube oil pre-heater, which in turn overheated the paint on the heater casing, causing smoke.
- The engineer carrying out the work noted his concerns with the operation of the heater. He shut down the system by activating the heater stop button, and had the intent to report a possible fault.
- Events overtook his intentions: the smoke activated the smoke detection system and raised the General Alarm.
- The root cause was discovered to be a failed switch in the safety cut-off mechanism, which was found to have failed in the “Reset” position; this meant that, even if the heater had tripped, it would have immediately reset itself thereby keeping the heater on.
What went right?
Positive points noted:
- Concerns were identified and support was sought in a timely way.
- When they heard the alarm, the duty engineer and chief engineer immediately activated both mechanical and electrical isolations, complete killing the system.
- The vessel was brought to Emergency Stations relatively quickly, despite communications problems.
- Investigation correctly identified the failed component and chain of events that led to the hazard.
- The vessel notified shore management in a timely way and provided full supporting information about the incident.
What went wrong?
- Emergency communications – vessel management had notified shore management of the recurring defect with the PA system, but repairs had been deferred and then cancelled.
- What happens when a real emergency occurs during a drill or exercise? There was no policy or guidance in place to deal with this possibility.
Actions
Particular actions taken:
- Investigation of similar systems to ensure no other latent failures or defects that may result in recurrence.
- Immediately pursue and action any outstanding defects related to communications and/or emergency response systems.
- Implement and publish a procedure for emergencies occurring during drills and exercises.
Related safety flashes
-
IMCA SF 14/11
23 December 2011
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.
The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.
All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.
IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.
The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.
Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.