Fire in engine room on platform supply vessel

  • Safety Flash
  • Published on 30 June 2014
  • Generated on 5 December 2024
  • IMCA SF 10/14
  • 3 minute read

A member has reported an incident in which there was a fire in the engine room on a platform supply vessel.

What happened?

The vessel was on its way to port from an oil platform, when it was decided on board to run a full power test on the propulsion system which included running all five diesel generators. This is a normal ‘routine’ conducted on board approximately every month according to the vessel’s planned maintenance system.

Subsequently the fire alarm was sounded on the bridge. The bridge called the engine control room. The chief engineer was in the engine control room where he already had started to prepare for the full power test. When the bridge called, he had already detected a fire located at diesel generator number 5 and confirmed this to the bridge. At the same moment he manually released the ‘flexi fog’ fire extinguishing system above the generator and started to shut down the propulsion engines. In the meantime the crew attended their muster stations and prepared themselves according to the vessel’s Emergency Plan.

After a short time the fire appeared to be extinguished by the ‘flexi fog’ fire extinguishing system. The Master decided to send down members of the crew wearing breathing apparatus (BA) sets. Initially this was not possible owing to smoke and fumes, but once the smoke and fumes had cleared they were able to enter. When they arrived at the fire area they discovered small flames above the generator which were rapidly extinguished using a fire hose.

Whilst there were no injuries, there was significant damage caused by the fire. A lot of power and signalling cabling was destroyed, resulting in the vessel losing propulsion and manoeuvring ability. A tug boat was ordered and the vessel was towed to a shipyard for repairs. This resulted in six weeks off hire for the vessel.

Damage to the engine room

Damage to the engine room following the fire

Damage to the engine room

Damage to the engine room following the fire

Broken nipple on lubrication pipe

The broken nipple on the lubrication oil pipe which led to the oil leakage

Our member’s investigation revealed the following:

  • The direct cause of the fire was discovered to be a broken lubrication oil pipe fitting leading from the generator’s engine block to a lubricating oil cyclone filter. This had resulted into an oil mist spraying out from the broken pipe. This oil mist was ignited by a source on the diesel generator or near by the generator
  • The root causes of the fire were determined to be:
    • Design weakness -The piping arrangement of the lubrication system had a weakness on a pipe nipple which resulted in to an oil leakage
    • Location of the smoke/fire detectors – When two of the fire detectors were activated the ‘flexi fog’ should automatically be released. It was considered that this did not occur because the fire was not detected by one of detectors above the generator -due to a poor location.

Our member took the following corrective actions:

  • The oil cyclone filter and associated piping was removed and the lubrication oil pipe connection on the engine block permanently blanked off. This was done after the manufacturer of the engine was consulted about the necessity of the lubrication oil cyclone filter.
  • The location and direction of the existing fire detectors was adjusted.
  • Additional fire detectors were installed in the engine room to ensure enhanced fire monitoring and detection.

Engine room fires form a recurring theme in IMCA safety flashes. Typically the root causes of such fires are failures in house-keeping or planned maintenance, or failure to recognise fire hazards and address risks. 

Latest Safety Flashes:

LTI: Finger injury during emergency recovery of ROV

A worker suffered a serious finger injury when their finger was caught between a crane wire and the recovery hook on an ROV.

Read more
BSEE: recurring hand injuries from alternative cutting devices

The United States Bureau of Safety and Environmental Enforcement (BSEE) has published Safety Alert 487.

Read more
NTSB: Crane wire failure

The National Transportation Safety Board of the United States (NTSB) published "Safer Seas Digest 2023".

Read more
Hot work performed outside of Permit to Work (PTW) boundary limit

A near miss occurred when a third-party contractor working removed a trip hazard from the vessel main deck, using a cutting torch and grinding disc.

Read more
Vital safety information (height of vehicle) found incorrect

“Height of vehicle” information displayed on a truck, was found to be incorrect.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.