Unreliable position reference systems leads to incident
- DP Event
- Published on 29 November 2019
- Generated on 5 November 2026
- DPE 04/19
- 1 minute read
Incident
Jump to:
The end-effect was that the deviation from the set point in surge and sway increased with each oscillation.
Comments
Only two DGNSS were online, with poor signal quality due to the location and environmental conditions. The end-effect was that the deviation from the set point in surge and sway were increasing for each oscillation.
Considerations
- For DP2 operations, the use of only two DGNSS systems is insufficient; a minimum of three systems are to be used based on two principles.
- The importance of monitoring the position reference systems (PRS) screen cannot be overstated; this then ensures that all the PRS agree on the position of the vessel.
- It is evident that the selected PRS were not providing reliable position information and highlights the problems that can be experienced when at least one reliable PRS is not available.
- It was noted that the move was paused at 2005; this should have provided the opportunity to investigate and correct the situation rather than continue with the move.
- It is also worth considering that the erratic movement of the vessel could indicate that the DP system needs retuning.
Latest DP incidents
-
Watch what you are pressing
While transiting away from a wind farm, the Master of a DP equipment class 2 vessel observed that the vessel was operating in Backup Mode and queried this with the bridge team and attending electrician
DPE 03/26
19 October 2026
Incident
-
The domino effect
The event demonstrates the importance of maintaining the approved DP power configuration, addressing known defects before equipment is relied upon during DP operations, and ensuring DP personnel understand how changes to the generating arrangement can affect redundancy and failure propagation
DPE 03/26
19 October 2026
Incident
-
Lost in calibration
During activity associated with calibration of a vessel Vertical Reference Unit (VRU), the DP control system experienced degradation of its attitude reference arrangement. Shortly afterwards, the vessel generated an Off Position Warning followed by an Off Position Alarm
DPE 03/26
19 October 2026
Incident
-
The UPS and downs
While a vessel was transiting in DP mode, the DPO observed the loss of Gyros 2 and 3 together with alarms from a 230V backup power supply. The telephone system remained powered but was inoperable.
DPE 03/26
19 October 2026
Incident
-
DP drill scenario – Consequence Analysis Class DP2 & DP3
DP drill scenario – Consequence Analysis Class DP2 & DP3
DPE 03/26
19 October 2026
Drill Scenario
The case studies and observations above have been compiled from information received by IMCA. All vessel, client, and operational data has been removed from the narrative to ensure anonymity. Case studies are not intended as guidance on the safe conduct of operations, but rather to assist vessel managers, DP operators, and technical crew.
IMCA makes every effort to ensure both the accuracy and reliability of the information, but it is not liable for any guidance and/or recommendation and/or statement herein contained.
Any queries should be directed to DP team at IMCA. Share your DP incidents with IMCA online. Sign-up to receive DP event bulletins straight to your email.