Aluminium fresh water tanks: Near collapse due to serious corrosion

  • Safety Flash
  • Published on 1 January 2002
  • Generated on 11 April 2026
  • IMCA SF 01/02
  • 2 minute read

During an owner’s annual inspection, serious corrosion attacks were found in integrated aluminium fresh water tanks, which required extensive repair.

What happened?

Brackets and stiffeners were found partly corroded through, as shown in figures 1 and 2. The corroded areas in the fresh water tank had to be partly renewed and repaired to an acceptable standard.

Transverse bulkheads and deckhead

Transverse bulkheads and deckhead

Bottom plating

Bottom plating

Probable Cause

The process for cleaning the fresh water tanks was considered to have been a major factor in the corrosion process. The fresh water tanks were sterilised annually, which exposed the tanks to a solution of hypochlorite for 12-24 hours. In addition, the shore-supplied water was frequently chlorinated, which meant that the tanks were frequently exposed to chlorides.

Even small amounts of hypochlorite can be very dangerous for aluminium, irrespective of the Al-alloy chemical composition, resulting in the development of serious pitting. Once pitting corrosion has started, it may continue to develop for a certain period if the tank is not properly washed with water after the application of hypochlorite. The filling and emptying of the tank is not sufficient to remove all the corrosion products. The reason for the corrosion attack is considered to be that the thin aluminium film on the surface is depolarised and locally broken down, in connection with the formation of chlorine released from the hypochlorite.

Lessons to be Learned

  • Hypochlorite or other chloride-containing chemicals should not be used for sterilisation of aluminium fresh water tanks if the tanks have not been fully coated.
  • In the case of uncoated aluminium fresh water tanks, other means of sterilisation than chloride-containing chemicals is needed, e.g. by using ultra-violet light.
  • If hypochlorite is used in coated tanks, it is essential that the tanks are thoroughly cleaned after the process. This is to minimised the change of corrosion occurring in the event of the coating breaking down.

Latest Safety Flashes:

MAIB: Sinking of tug Biter with loss of two lives

MAIB has published Accident Investigation 17/2024 relating to the girting and capsize of tug Biter with the loss of two lives.

Read more
Dropped object – strop parted over sharp edge

A cylinder was lifted to a height of approximately 6 metres over deck of the vessel, the sharp steel edges of the cylinder cut through the firehose protection and caused the strop to part.

Read more
Person injured when pry bar slipped

A crew member who was applying downward pressure to their pry bar to lift a track, fell towards the deck when the pry bar slipped.

Read more
MSF: High potential near miss during FRC maintenance

The Marine Safety Forum has published Safety Alert 26-01 relating to an incident where there was an unplanned lowering of an FRC to the sea

Read more
BSEE: Crane incident leads to serious facial injuries

BSEE has published Safety Alert 512 relating to a crane incident during well abandonment which led to a worker being struck and suffering serious facial injuries.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.