MSF: LTI – Engineer scalded

  • Safety Flash
  • Published on 22 January 2024
  • Generated on 7 December 2025
  • IMCA SF 02/24
  • 3 minute read

An engineer received severe scalding injuries when working in the engine room.

What happened?

The MSF published Safety Alert 23-14 in which an engineer received severe scalding injuries when working in the engine room. The incident occurred during operations on a platform supply vessel (PSV).  The engine alarm system was activated due to low level in the high temperature cooling water circuit on one diesel generator. The engineer examined the generator and identified a leak from one of the rubber compensators. He installed a new compensator and began filling the system with water. He went down to inspect the newly installed compensator to ensure it was not leaking. While standing in front of the compensator, another nearby compensator burst and the engineer was exposed to a blast of steam and scalding water. The engineer suffered partial thickness burns to the face and upper body. First aid treatment was administered on site and he was medevac’d to hospital. He made a full recovery after spending some time in hospital.

Screenshot 2024 01 22 104535

What went wrong?

The following is the MSF’s summary of the several human factor and organization causes for the incident.

  • The pressure in the cooling water system rose suddenly when the cold water was added to the hot system. This raised pressure exceeded the installed compensator’s structural integrity.
  • The installed compensator did not have the correct temperature rating for the system it was installed on.
  • There was no maintenance or replacement history on the compensator since the vessel was built (10yrs ago).
  • The compensator material likely degraded and weakened overtime due to the incompatible temperature rating.
  • The cooling water system had a pressure relief valve; however, it was perhaps not rated sufficiently and could not deal with a sudden pressure increase.
  • The manufacturer’s procedure for filling the system while still hot was not followed. The system needed to be cooled before being filled with water.

Actions

  • The primary corrective action was to ensure the compensators are rated for the media, pressure, and temperature of the system they are installed on.
  • The compensators should also be checked to ensure they are not misaligned and are installed within manufacturer’s specifications.
  • OEM procedures and instructions should be followed; this particularly so in this context of filling a high temperature cooling water system with water – time should be allowed for it to cool down to avoid a sudden increase in pressure.
  • An appropriate inspection and maintenance plan to be implemented for this type of equipment. 

Latest Safety Flashes:

Vessel ran aground

A vessel on a short voyage ran aground while navigating through a narrow channel at low tide.

Read more
Fire in the engine room – fuel spray fire

A fire broke out on the starboard main engine due to a leak from the fuel pipe connection.

Read more
Fire hazard: missing splash tapes on fuel hose connections

It was observed that several engine fuel hose connections were not fitted with splash tapes.

Read more
Dropped pallet during cargo transfer

A plastic pallet loaded with plastic lube oil drums fell while being hoisted.

Read more
Positive – Enhancing safety communication through digital monitors

All crew and office personnel have 24/7 access to essential safety and operational updates.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.