Battery explosion during routine maintenance
What happened
A chief engineer suffered minor injuries in a battery explosion when disconnecting a cable from the battery. The incident occurred onboard a harbour tug. The chief engineer was planning to replace a battery disconnect switch that had failed. While disconnecting the positive terminal, both terminals were inadvertently short-circuited with a spanner and the battery exploded causing injuries to the chief engineer. Operations were stopped, first aid was given and the tug returned alongside. After assessment at hospital the chief engineer returned to the tug with only minor injuries. The tug was out of service for four hours.
What went right?
- The external power supply breaker was switched off;
- To be able to work on the switch safely, it was decided to disconnect the battery cables so the switch would be isolated from the battery 24VDC.
What went wrong
The battery was inadvertently short-circuited with a spanner.

Lessons learned
- Protect battery terminals with plastic caps to avoid accidental contact;
- Ensure proper PPE (gloves, apron, face shield) is used when working on batteries;
- Consider the use of tools appropriate for battery handling;
- Changes to vessel planned maintenance system:
- Follow manufacturers recommendations for battery maintenance
- Increase the frequency of battery maintenance inspection to gain better control of batteries in a poor state;
- Consider the installation of battery chargers with temperature sensors.
Members may wish to refer to:
Safety Event
Published: 27 February 2023
Download: IMCA SF 06/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.