Electrical flash burns
We have recently learned of this incident which occurred on an offshore installation. An electrician suffered superficial flash burns to his face, neck, ears and hands while operating a Merlin Gerin DA-type circuit breaker which was one of three incoming feeds to the platform 440v switchboard. The breaker was in the service position and attempts were being made to close the breaker and energise the switchboard. Difficulties had been experienced in closing the circuit breaker due to a defective component in the closing control circuit. This led to the use of an unapproved procedure, which had not been risk assessed.
The injured party had been standing at the circuit breaker with the panel door open and was using a tool to simultaneously overcome the defect while operating the ‘close’ push button on the front of the circuit breaker. While carrying out this action, the tool came into contact with live power circuit conductors which initiated an arcing fault and exposed the injured party to the dissipation of a high energy source.
The company involved has recommended to its personnel that:
- users review procedures to ensure that any undocumented operations that have become custom and practice are subjected to a risk assessment;
- uses should ensure that all equipment malfunctions that require override procedures to obtain functionality are subjected to risk assessment;
- all design safety features of equipment should be utilised.
Safety Event
Published: 1 April 2000
Download: IMCA SF 02/00
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.