Engine room fires – Appropriate use of insulating material on hot surfaces
Safety flash 10/05 reported on a recent Engine room fire. It was noted in that safety flash that the probable cause of the fire was spraying of leaking hydraulic oil onto an improperly insulated exhaust flange. (NB SOLAS regulations require proper insulation of all surfaces with temperatures above 220°C.)
A member has provided some useful feedback on the incident report, set out below for further information:
- Covering every hot surface with lagging could increase the risk of fire if done so without using suitable insulation material;
- The use of soft or absorbent lagging can create further potential risk, since oil sprayed onto absorbent or soft lagging on a hot exhaust can eventually ignite;
- A small leak might dribble unnoticed onto soft or absorbent lagging until there is enough oil in close proximity to the hot exhaust to cause a fire. This can be an issue with certain widely used makes of engine;
- Oil resistant laggings are commercially available. Whilst these are not perfect, they do afford some protection from oil spray or leaks. These oil-resistant lagging types have a silver facing to protect against flammable liquids.
Safety Event
Published: 30 November 2005
Download: IMCA SF 11/05
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.