Equipment starts unexpectedly
What happened
THree mechanics obtained a Lock-out/Tag-out (LOTO) for a High voltage AC unit, and were performing routine maintenance on the unit. As one of them went to lubricate the bearings, the machine started unexpectedly. Work was stopped and a review was conducted. It was discovered that a linkage was broken in the circuit breaker handle and the breaker did not actually shut off when arranging the LOTO. The plant electricians repaired the linkage, the LOTO was rehung, and the work was completed.
What went right and/or wrong?
- What went right: no one was in the line of fire when the machine restarted and there were no injuries;
- What went wrong: equipment failure – the linkage in the breaker handle was broken.
Lessons learned
- Carefully check that equipment is de-energized before working on it – prove that it is “dead”;
- Ensure a full and thorough understanding of isolation and ensure the proper sources of energy are isolated when equipment is upgraded or modified.
IOGP Life-Saving Rules applicable
- Energy Isolation: the mechanics did not:
- Identify all energy sources;
- Confirm that hazardous energy sources were isolated, locked, and tagged;
- Check there was zero energy; did not test for residual or stored energy.
- Work Authorisation: the mechanics did not:
- Confirm that hazards were controlled or that it was safe to start
Members may wish to refer to:
Safety Event
Published: 3 May 2023
Download: IMCA SF 11/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.