Failure of fire extinguishers owing to corrosion
A member has reported a near miss incident in which a fire extinguisher failed due to corrosion of the internal stem. The failure was discovered during inspections of fire extinguishers during a mobilisation. Corrosion had taken place where the brass fitting connected to the aluminium stem. The extinguisher was relatively new and this was its first inspection. On removal of the pillar valve, the technician noticed an unusual amount of corrosion around the internal female brass fitting connecting the aluminium stem to the internal male thread of the pillar valve. The technician touched the stem and it fell apart at the corroded area. The internal inspection of the cylinder found that it was in good condition with no signs of corrosion.
Members are reminded of the corrosion potential with dissimilar metals, particularly in the case of pressure vessels. Our member notes that had the fire extinguisher been required for use in a hyperbaric chamber all that would have happened would have been a release of gas when operated. Our member is in direct contact with the supplier to try and resolve the issue.
Members may wish to refer to the following incidents (search words: extinguisher):
Safety Event
Published: 6 May 2016
Download: IMCA SF 12/16
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.