- IP Code: Mandatory Code enters into force on 1 July. Make sure your company is up to speed with the changes.
- Early Bird tickets available for the IMCA Global Summit 2024. 3-4 December, Utrecht, Netherlands. Members can save £400.
- Discover how we are helping Members reduce emissions: Explore the ProjectGHG hub now.
- Now booking. Join the Lifting and Rigging community at our Technical Seminar in Amsterdam. Thursday 12 September 2024
- Now booking. Underwater Ship Husbandry Seminar. 10 October 2024, Singapore.
MSF: CO2 system left non-operational after servicing
What Happened
The Marine Safety Forum has published Safety Alert 22-10 relating to an important safety system being left non-operational after it was serviced. The incident happened when a vessel had recently undergone a firefighting equipment survey. All equipment was fully inspected, and any faults or discrepancies were rectified. The Fixed CO2 system flexible hoses were renewed. To allow the survey to be conducted safely, safety pins had been put in place, while the outside contractors carried out their inspection. When finished these should have been removed, to make the system ready for activation – but they weren’t.
Almost 4 weeks after the survey, after a routine inspection, it was found that the safety pins inserted during the survey had not been removed and were still in place making the system inoperable. This had a high potential to develop into a serious incident if the CO2 system had been required for extinguishing an engine room fire.
A similar safety alert had been issued by the vessel owner to their fleet in August 2021.
![](https://imcaweb.blob.core.windows.net/wp-uploads/2022/07/Screenshot-2022-07-26-143910.jpg)
What went wrong
Exact details on causes and corrective actions specific to this incident were not provided by the submitting party / vessel owner, but lessons learned, and actions below were reinforced from the previously mentioned fleet safety alert that had been issued in August 2021. This guidance was relevant to the incident described.
It should be noted that the recommendations were specific to that vessel owner; each vessel or company should review against their own processes.
Lessons learned
- Use of a Permit to Work may be considered for any maintenance work on essential fire fighting equipment – or indeed any essential safety system which if inoperable, might be potentially life-threatening;
- Careful control and records should be kept of the isolation of such equipment to help ensure that the system cannot be left in an inoperable condition;
- Never assume and rely that all will be well and ok. Assumption is the pathway to undesired events. Always check and verify;
- Ensure thorough inspection of third-party work to ensure any systems worked on are reinstated to original design intent after completion of the task;
- Work is only complete when the isolations are removed, and the permit can be closed.
The MSF notes that this is a example of Safety Flashes / Lessons Learned, issued by the company, not being acted upon, distributed, or reviewed by all crew members.
- Safety information issued by shoreside or vessel management should be fully discussed, circulated to all crew members, and acted upon, as required to maintain the safety of all onboard the vessel. This should include all circulars, Safety Flashes, lesson learned, and outside bulletins = all should be suitably posted, discussed and noted by all crews;
- Include such safety briefing, material and alerts in hand over notes to ensure your colleagues are also properly informed;
- Could a similar occurrence happen on your vessel?
Members may wish to refer to:
Safety Event
Published: 26 July 2022
Download: IMCA SF 19/22
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.