Near miss with high pressure gas due to incorrect procedures
What happened
A crew narrowly avoided potentially serious problems with a high pressure gas supply by stopping and thinking things through. The near miss occurred whilst a crew were setting up for pigging of high pressure gas mains lines. A change to the flow configuration on two high-pressure gas mains to test flow rate was required; on the second to last step of the procedure, they closed a valve at the valve set.
Since one employee was unfamiliar with the location because it was not in their work area, they questioned the operator at the location to clarify what closing the valve actually did to the system flow. After a brief conversation they realized that closing the valve would actually isolate the pipeline and prevent the flow of gas to a downstream valve set that they were intending to flow to.
Work was stopped immediately and the valve returned to its normal position
What went right
After returning the valve to normal position, all parties involved at the location reviewed the procedure and figured out what went wrong. They discovered that the procedure was written using an old drawing of the valve set and did not represent the current valve configuration.
At that point all work was stopped, and valve sets were returned to normal until the procedure was updated using the correct drawings for the site.
Had they continued with following the incorrect and outdated procedure, they would have caused a compressor station to trip on low suction and possibly created other downstream supply issues.
Members may wish to refer to:
Safety Event
Published: 3 August 2023
Download: IMCA SF 19/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.