- IP Code: Mandatory Code enters into force on 1 July. Make sure your company is up to speed with the changes.
- Early Bird tickets available for the IMCA Global Summit 2024. 3-4 December, Utrecht, Netherlands. Members can save £400.
- Discover how we are helping Members reduce emissions: Explore the ProjectGHG hub now.
- Now booking. Join the Lifting and Rigging community at our Technical Seminar in Amsterdam. Thursday 12 September 2024
- Now booking. Underwater Ship Husbandry Seminar. 10 October 2024, Singapore.
Short circuit on 440v AC bus bars – arc flash
What happened?
A crewman was doing electrical work on a 440v power distribution panel (PDP), when a loose earth bonding cable made contact with a live 440v bus bar causing a short circuit and an arc flash. Whilst the crewman was using cable ties to fix loose cables within the panel, he observed a loose earth bonding cable in poor condition. He made up a new earth cable from 6mm wire, and whilst he was attempting to re-connect the earth bonding cable, the loose trailing end of the earth bonding cable came into contact with the 440Vac bus bar. A short circuit between the 440Vac and the Earth bonding cable was observed resulting in an arc flash.
At the time there were no injuries nor damage to equipment. The crewman reported the incident to his line manager, reporting that he felt shaken by the incident and felt his heart racing. He was sent to his cabin to rest.
Subsequent to the incident, the crewman reported experiencing blistering on his hands and attended a walk-in medical centre where he was diagnosed with partial thickness burns to his face. He was assigned light duties for two weeks.
What went wrong?
- Crew deliberately ignored safety protocols to expedite what was considered an easy and straightforward task:
- one job was started (supervising the installation of a welding cable) but then changed to another job. The injured person did not discuss this work with his supervisor, nor carry out a risk assessment, TBT or raise a PTW for the work
- there had been a generic toolbox talk (TBT) completed but work on the PDP was not mentioned;
- This incident was not reported in a correct or timely way, denying the injured person access to immediate medical attention which may have mitigated his injuries.
What lessons were learned?
- There was inadequate supervision with regards to compliance with electrical safety control measures;
- The risk of unauthorised access to the power distribution panel (PDP) had not been properly assessed;
- The panel had inadequate insulation of terminals which remained live when panel was opened, this may have been broken off or removed over time.
What actions were taken?
- Access to electrical cabinets should be restricted;
- Electrical safety audit conducted on-board vessel;
- Risk assessment to be re-written to include mitigations to identified hazards;
- Further incident reporting and investigation training to be delivered to vessel crew.
Members may wish to refer to:
Safety Event
Published: 19 February 2020
Download: IMCA SF 06/20
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.