UK HSE: Liquid petroleum gas (LPG) leak
The UK Health and Safety Executive (HSE) reports that the operator of the UK’s largest oil refinery has been fined for health and safety breaches after a leak of liquid petroleum gas (LPG) was discovered by a worker cycling home at the end of their shift. See press release here.
What happened?
There was an uncontrolled release of around 15 tonnes of LPG through a valve near to the main roadway used by LPG road tankers visiting a refinery in Fawley, Hants, UK. The leak went undetected for around four hours before being discovered by an employee on his way home. It took a further hour to establish the source of the leak with on-site emergency personnel having to enter the area to reset the valve.
What went wrong?
An investigation by the Health and Safety Executive (HSE) found that the leak occurred because:
- LPG was put through the pipe work at too a high a pressure for the valve;
- There was no process in place to detect the discrepancy in the flow in the pipe;
- The company had failed to take all measures necessary to prevent a major incident.
The inspector said “The measures required to prevent incidents should be proportionate to the risks. Where companies handle large quantities of substances that can cause major incidents, such as LPG, they are required to have layers of protection in place to prevent incidents.
In this incident a number of those layers either failed or were not in place resulting in a significant leak. Even though there was no fire or injury on this occasion, there was potential for a major incident. The prosecution has been brought to highlight the importance of maintaining the layers of protection and preventing this kind of major leak.”
(IMCA emphasis)
Safety Event
Published: 28 February 2022
Download: IMCA SF 05/22
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.