Skip to content

Unexpected Release of Water During Annual Maintenance of CO2 Fixed Firefighting System

What happened

An incident took place during annual maintenance of CO2 fixed firefighting equipment on a vessel, in the emergency generator switchboard room. There was an unplanned and unexpected release of water.

As part of the annual maintenance of the CO2 fixed firefighting system, air was blown at 7 bar through the lines. As part of this check, a person was located in the CO2 room on the starboard side of the main deck, an engineer was in the emergency generator room located below the switchboard and the vessel electrician was in the switchboard room to witness the tripping of the emergency generator room supply fan.

What went wrong?

When the task started, a fine mist was noticed coming from one of the nozzle heads in the emergency generator switchboard room. Further to this, water was seen spraying out of the nozzles onto the 440V and 220V switchboards, transformers and surrounding areas. An all stop was immediately called over the radio.

What were the causes?

The source of the water has not been identified, however it is suspected to have been as a result of condensation forming in the pipework supplying the nozzles. These pipes are of considerable length.

IMCA notes that compressed air systems should be blown through before connection, to ensure that there is no water in the air system which may be transferred into the system being blown through.

What actions were taken?

Following the incident, the vessel team placed bags with a small air vent onto the nozzle heads to collect any unexpected release of water during checks;

  • Nozzle heads to be covered appropriately during these tests;
    • the planned maintenance system was updated to include instructions to cover nozzles within electrical switchboard spaces and any other sensitive areas during these tests;
    • other vessels and third-party contractors were advised to take similar precautions.

Members may wish to refer to the following incident:

Safety Event

Published: 19 March 2018
Download: IMCA SF 06/18

Relevant life-saving rules:
IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.