MSF: Grub screws and perished valves – trouble with methanol transfer
- Safety Flash
- Published on 23 October 2020
- Generated on 7 April 2026
- IMCA SF 30/20
- 2 minute read
Jump to:
The Marine Safety Forum (MSF) has published Safety Alert 20-06 relating to problems with methanol transfer caused by problems with grub screws and perished valves. A vessel was advised by an installation of a discrepancy in the quantity of methanol received compared to what was expected.
What happened?
Investigation revealed that these discrepancies whereby a quantity of methanol was unaccounted for, had been occurring for years.
Unknown to the crew, during the transfer of methanol to the installations, a quantity of the methanol was also being discharged to sea via the system flushing line.
This was possible as a spool piece was incorrectly left in place and two valves either side of the spool piece were passing fluid.
What were the causes? What went wrong?
One rubber valve was found to be perished and the other Teflon valve was found with signs of corrosion. On closer inspection it was found that a grub screw, for limiting the movement of the gears was too far in and was restricting the range of movement. This resulted in the Teflon valve not closing fully and had been that way most likely from new-build.
The MSF’s member identified the following root causes:
- insufficient knowledge of the methanol cargo system
- insufficient planned maintenance
- insufficient transfer procedures in place
- poor communication.
Actions and recommendations
- Proper and recorded confirmation from the receiving installation that they have received the correct quantity of cargo.
- Review cargo systems or any appropriate liquid transfer systems to ensure that any set-up designed to avoid discharge to sea is correctly in place.
- Update planned maintenance system.
Members may wish to refer to:
- “The Carriage of Methanol in Bulk Onboard Offshore Vessels” recently published in conjunction with Oil Companies International Marine Forum: https://www.marinesafetyforum.org/guideline/the-carriage-of-methanol-in-bulk-onboard-offshore-vessels/
Related Safety Flashes
-
IMCA SF 04/10
14 July 2010
-
IMCA SF 07/07
14 August 2007
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.
The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.
All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.
IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.
The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.
Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.