Unintentional selection of manual mode
- DP Event
- Published on 27 February 2018
- Generated on 7 November 2026
- DPE 01/18
- 2 minute read
Incident
Jump to:
The incident highlights the importance of vessel operators risk assessing the DP control station and taking appropriate action as necessary.
Comments
- Initiating event: Inadvertent selection of manual mode whilst in full DP mode.
- Main cause: Human factors – The vessel mode of operation was changed from automatic DP mode to manual DP mode by a double press of the DP manual position button.
- Secondary cause: Computer – No additional barrier (e.g. notification) when manual position selected.
The vessel operator reported that there was an upgrade available to warn the DPO of the change of DP control status and therefore provide additional protection against accidental change of DP control status. The report concluded that all company vessels would be upgraded to include this function.
Considerations
- It is important that DPO training focuses on good practice, an action should be followed up continuously to verify the intention of the action is reached or being executed.
- This type of event has happened on other DP vessels, it is noted that some vessel operators have fitted a cover or made mode of operation buttons stand out from others.
- The incident highlights the importance of vessel operators risk assessing the operation of the DP control station and taking appropriate action as required.
- Consideration should always be given to using joystick auto heading, which can provide tighter control of the vessel, prior to switching to individual manual control of the thrusters.
Latest DP incidents
-
Watch what you are pressing
While transiting away from a wind farm, the Master of a DP equipment class 2 vessel observed that the vessel was operating in Backup Mode and queried this with the bridge team and attending electrician
DPE 03/26
19 October 2026
Incident
-
The domino effect
The event demonstrates the importance of maintaining the approved DP power configuration, addressing known defects before equipment is relied upon during DP operations, and ensuring DP personnel understand how changes to the generating arrangement can affect redundancy and failure propagation
DPE 03/26
19 October 2026
Incident
-
Lost in calibration
During activity associated with calibration of a vessel Vertical Reference Unit (VRU), the DP control system experienced degradation of its attitude reference arrangement. Shortly afterwards, the vessel generated an Off Position Warning followed by an Off Position Alarm
DPE 03/26
19 October 2026
Incident
-
The UPS and downs
While a vessel was transiting in DP mode, the DPO observed the loss of Gyros 2 and 3 together with alarms from a 230V backup power supply. The telephone system remained powered but was inoperable.
DPE 03/26
19 October 2026
Incident
-
DP drill scenario – Consequence Analysis Class DP2 & DP3
DP drill scenario – Consequence Analysis Class DP2 & DP3
DPE 03/26
19 October 2026
Drill Scenario
The case studies and observations above have been compiled from information received by IMCA. All vessel, client, and operational data has been removed from the narrative to ensure anonymity. Case studies are not intended as guidance on the safe conduct of operations, but rather to assist vessel managers, DP operators, and technical crew.
IMCA makes every effort to ensure both the accuracy and reliability of the information, but it is not liable for any guidance and/or recommendation and/or statement herein contained.
Any queries should be directed to DP team at IMCA. Share your DP incidents with IMCA online. Sign-up to receive DP event bulletins straight to your email.