Attempted service to microwave results in fatal electrocution
An experienced electrician (12 years with the company) opened up a microwave in order to service it, in spite of dire warnings not to do so. A warning label, prominently displayed on the machine, clearly indicated the potential for high voltage as follows:
“Warning – High voltage and microwave energy. Do not remove any cover. Caution – Always disconnect the mains plug from the wall socket before servicing. The unit contains no user-serviceable parts. Refer servicing to authorised personnel. This unit contains dangerous voltages.”
He put a tester across the disconnected leads with the power on (several thousand volts). The current went to the ground through his body, via the ice-making machine next to where he was working – burn marks confirm this. The incident resulted in a fatality.
To address this incident, the company has issued the following instruction to its personnel:
“With immediate effect the on-site repair of domestic equipment which contains high voltage components is strictly prohibited (such equipment includes microwave ovens, television sets, PC monitors, electrical insect killers, etc). These types of equipment should be returned to an authorised vendor for repair.”
Safety Event
Published: 3 July 2003
Download: IMCA SF 08/03
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.