- IP Code: Mandatory Code enters into force on 1 July. Make sure your company is up to speed with the changes.
- Early Bird tickets available for the IMCA Global Summit 2024. 3-4 December, Utrecht, Netherlands. Members can save £400.
- Discover how we are helping Members reduce emissions: Explore the ProjectGHG hub now.
- Now booking. Join the Lifting and Rigging community at our Technical Seminar in Amsterdam. Thursday 12 September 2024
- Now booking. Underwater Ship Husbandry Seminar. 10 October 2024, Singapore.
High potential near miss: person found unconscious in confined space
What happened?
During commissioning activities, a commissioning engineer was found unconscious inside a gas valve unit (GVU). He received CPR and regained consciousness before being transported to the hospital for further diagnosis. Luckily, he has made full recovery.
![](https://imcaweb.blob.core.windows.net/wp-uploads/2021/07/image1.png)
Pressure holding tests were being conducted, controlled from an interface cabinet. Nitrogen gas was used as the test medium. The pressure build-up was taking longer than usual so the vendor performing the test suspected that there was a leak somewhere. He heard a hissing sound coming from inside one of the GVUs (where the piping runs through) and suspected that the leak was coming from the piping inside the GVU. The vendor informed the commissioning engineer about the leakage and returned to the interface cabinet. Shortly afterwards the vendor noticed the commissioning engineer entering the GVU through the manhole opening. The vendor rushed to the GVU, but the commissioning engineer was already overcome by the nitrogen and had collapsed inside the unit.
The commissioning engineer was rescued, CPR was administered, and he regained consciousness before being transported to the hospital supported by additional oxygen. The engineer has since made a full recovery and is back on duty.
What went wrong?
- The gas valve unit (GVU) is clearly a confined space; however, the experienced engineer decided to enter alone via the manhole opening;
- There were no confined space entry controls in place at that particular GVU i.e.:
- no confined space entry permit in place
- no atmospheric test results at the location
- no safety watch in place.
What lessons were learned?
Never enter a confined space unless a permit is active, and all controls are in place to ensure your safety, such as; the atmosphere has been successfully tested; a safety watch is at the entrance; you know what the rescue plan is; and you have discussed your entry with your supervisor.
Members may wish to refer to:
Safety Event
Published: 18 June 2019
Download: IMCA SF 14/19
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.