LTI: crew member crushed finger when opening fire flap
What happened
A crew member injured his finger while opening an emergency fire flap. The incident occurred after an annual test of the deluge system during which the emergency fire flaps had to be closed. Two crew members were releasing the securing butterfly nuts on the fire flap for the emergency generator. The final nut would not release owing to air pressure on the flap. A rope was attached to the hatch and pulled to reduce the pressure, to allow the butterfly nut to be released and to prevent potential uncontrolled swing of the hatch due to pressure build up. As the last butterfly nut was released, one of the workers got his index finger accidentally jammed between the hatch door and the frame as his colleague was still pulling the hatch in the opposite direction. His finger was crushed; he was sent ashore to hospital, where X-rays revealed a broken finger.

What went wrong
Our members’ investigation noted the following:
- Risk seen as tolerable – the work party considered the work to be safe. There was inadequate understanding of the risks involved: opening and closing of fire flaps was not captured during Toolbox Talks, nor in the Risk Assessment for the annual inspection on the deluge system;
- There was a lack of proper planning, and there were inadequate resources – the weight of hatch door was not taken into consideration when assigning the job. Also an inappropriate tool was used (a rope) to ease the pressure on the nut;
- No Stop Work authority was exercised – The job should have been stopped and reassessed when the team came across difficulty in releasing the nut.




Lessons learned
- Ensure suitable and sufficient risk assessment is conducted for all tasks, whether routine or non routine, and that all aspects of the task are covered;
- Ensure all personnel involved in any operation are properly briefed in detail during toolbox talks regarding hazards associated with the task, and controls in place to ensure safe and smooth operation;
- Risk Assessments and toolbox talks are not one-way conversations, but an opportunity for ALL team members to speak up and ask questions, discuss the task, ensure all control measures are in place and that everyone is clear on their duties and responsibilities during the job;
- If you need to change things, don’t just carry on: exercise the Stop Work Authority. Stop, step back, and reassess the task to find a safer, easier alternative;
- Understand “Line of Fire” – see IMCA short video here and longer video here.
Members may wish to refer to:
Safety Event
Published: 16 February 2023
Download: IMCA SF 05/23
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.