MAIB: A scalding injury
What happened
The Marine Accident Investigation Branch Safety Digest 2/2022 includes an incident in which an engineer suffered severe scalding to his face. The incident occurred during rounds, when a cruise ship’s third engineer discovered a leak on the drain valve for one of the vessel’s four economisers. There was an open-ended pipe running from the valve to a tundish drain in the deck. The Chief Engineer was briefed and a decision was taken to conduct a repair. The economiser’s circulating pump was stopped and the inlet and outlet valves were shut; the plan was to leave the system to cool down overnight before the repair.

What went wrong
After the isolations were in place, but before the system had cooled down, the Second Engineer decided to check the system by opening the drain valve. Leaning over the valve, the Second Engineer cracked it open and pressurised hot water and steam burst out of the drain pipe. The force of the discharge caused the hot water to deflect upwards off the tundish, severely scalding his face. After initial medical treatment on board, he was evacuated to a nearby hospital for specialist burns care.
The lessons (MAIB)
- Hazard: The opening of drain lines on pressurised systems should be undertaken with extreme caution;
- Risk: The Second Engineer leant forward over the pipework that ran to the tundish to open the drain valve. As a result, his upper body was directly in line with the deflected water and steam. When venting or releasing stored pressure, keep your body OUT OF THE PATH of any predictable discharge;
- Equipment: Take great care when opening valves that are infrequently used. A valve that has become seized in the shut position may require extra force to manoeuvre it and lead to the valve suddenly and unexpectedly opening, causing an uncontrolled fluid flow. The use of a correctly sized wheel key can provide appropriate torque and increase the application of controlled force to the valve wheel.
Members may wish to refer to
Safety Event
Published: 30 November 2022
Download: IMCA SF 27/22
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.