Near-miss: Fire hazard from leaking fuel supply line
What happened?
A potential fire hazard was discovered, caused by a failed fuel pipe connection on the supply line to the main engines. The Chief Engineer was called to engine room with a report of a leak on a low pressure fuel supply line supplying both main engines. Upon arriving in the engine room and assessing the situation, a temporary repair was effected, due to being unable to isolate the pipe. Self-amalgamating tape was used to reduce the leak to a weep and then fibre-glass resin and bandage was applied, to try and seal the weep.
At the time, both main engines were running with the starboard engine on load, although the port propeller was declutched. Three auxiliary engines and all the thrusters were on load.
![](https://imcaweb.blob.core.windows.net/wp-uploads/2017/05/sf121.png)
![](https://imcaweb.blob.core.windows.net/wp-uploads/2017/05/SF122.png)
What were the causes?
The immediate cause was found to be a failed weld on a T-piece of the pipe. The root cause is believed to be the age of the pipe, an original fit from the vessel’s construction, incurring natural degradation over time.
Actions taken and lessons learnt
- The leak was discovered early as a result of due diligence and good watchkeeping, which allowed for a controlled temporary repair;
- The vessel notified shore management as soon as possible after the incident, providing detailed Incident reports, supporting information and photographs;
- Vibration, owing to the proximity of the main engines, is going to be an issue with equipment of this sort. Engineers should maintain awareness of equipment shortcomings and manufacturing design weaknesses;
- As such failures cannot always be predicted and vessels should always carry appropriate pipe repair solutions such as plastic steel, fibre glass resin, pipe repair clamps etc.;
In this case, a trend in the failure of fuel supply piping was noticed; this was the 4th failure within 4 months.
Members may wish to refer to the following incidents:
- Cracked fuel line results in an engine fire
- Fatal engine room fire on suction dredger Arco Avon[cause of death: the third engineer was attempting to repair a failed fuel pipe when fuel, under pressure in the pipe, ignited]
- Near miss: Fire hazard arising from failed fuel pipe connection
Safety Event
Published: 25 May 2017
Download: IMCA SF 12/17
IMCA Safety Flashes
Submit a Report
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding [email protected] to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.
IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.
IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.