Wire break in wind sensor caused DP drive-off

  • Safety Flash
  • Published on 9 October 2006
  • Generated on 22 February 2026
  • IMCA SF 12/06
  • 2 minute read

A Member has reported an incident in which one of its vessels suffered a DP drive-off during valve monitoring operations in open water.

What happened?

The wind was light – 5-10 knots – and there was good visibility. The vessel was on DP, with 2 x DGPS, 2 x taut wires and two wind sensors selected in the system. An ROV was in the water and the diving bell was on the surface with diving operations completed.

The DP operators noticed an increase in the thruster pitch followed by an ‘off position’ warning, whereupon both DGPS were deselected. The operators then noticed that one wind sensor was reading 60 knots – clearly an error – while the wind speed registered on the DP console was 35 knots as an average of the two sensor speeds.

The errant wind sensor was deselected immediately and the vessel position then stabilised at 17m from the original set-point.

The following points were noted on completion of the investigation:

  • The cabling for the failed wind sensor had been routed through a junction box which had suffered water ingress due to a failed seal, effectively leading to a wire break.
  • Tests showed that the errant wind sensor failed to zero or failed to maximum (60 knots) dependent upon where the wire was broken. The other wind sensors were wired differently and failed to zero at all times.
  • One wind sensor had been deselected automatically as a function of the DP software, as it was registering less than 5 knots. Had three sensors been in the system, the DP would have rejected the errant signal.
  • There was no alarm for the operators and the location of the manual readouts was poor in relation to line of sight for the DP operators.
  • This particular failure mode of the sensors was not covered by the failure modes, effects and criticality analysis (FMECA).

The company concerned took the following actions:

  • Changes to wiring of errant sensor (a filter) to prevent recurrence of ‘failure to maximum’.
  • DP software upgrade to include a discrepancy alarm.
  • Wire break tests conducted throughout the company’s fleet to see if the problem exists elsewhere.

The potential for a serious accident has led to this DP incident being distributed as a safety flash.

Latest Safety Flashes:

Fall from height during mooring due to rope tension reaction

Rope became entangled with the propellor during mooring operations of a tanker causing the operator to lose balance and fall onto the lower platform.

Read more
Missing protection – progressive wear on hydraulic hoses causes damage

During an inspection, several hydraulic hoses and fuel hoses were found in direct contact with surrounding surfaces and sharp edges.

Read more
Small engine room fire – flammable object ignited

While ramping up the starboard main engine, a small flammable foreign object ignited.

Read more
Positive: damage to Fast Rescue Craft davit wire rope caught before failure

During routine checks, it was observed that the FRC davit wire rope had a visible fracture at the socket termination area.

Read more
BSEE: Miscommunication and trapped pressure causes injury during valve maintenance

BSEE has published Safety Alert 509 relating to a gas release incident on an offshore platform.

Read more

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.

The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.

All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.

IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.

The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.

Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.