Flash fire on Oxygen gas quad hose
- Safety Flash
- Published on 22 July 2022
- Generated on 27 November 2026
- IMCA SF 18/22
- 2 minute read
Jump to:
There was a flash fire on an Oxygen hose line onboard a DSV.
What happened?
The incident occurred during routine checks, when an LST (Life Support Technician) reported that the Oxygen supply pressure to dive control was low (25 Bar). SAT control informed Dive Control and agreed that a new Oxygen supply was required. The LST went to the appropriate quad (on the main deck), and started by closing the row of eight bottles of Oxygen before opening a new row. Whilst opening the new row of Oxygen supply bottles the LST heard an unfamiliar noise (a flapping sound from the regulator) and immediately closed the cylinder pillar valve and closed the valve on both regulators (SAT control and reclaim regulator valve) and quickly moved away from the Oxygen quad. The LST immediately returned to SAT control and reported to his supervisor.
Shortly afterwards, the Oxygen hose burst followed by an explosion and flash fire at the reclaimed Oxygen hose line. The deck foreman who investigated the source of the explosion immediately extinguished the fire with a dry powder fire extinguisher. There was no damage found on the nearby gas quads apart from the affected hose and regulator.
What went wrong – investigation findings
Investigation showed that the bullnose inlet (connection to the pillar valve) had no filter to stop rust contaminant from the cylinder going into the regulator. Small particles of rust from inside the cylinder accumulated inside the regulator causing high friction after the Oxygen release, resulting in heat and contributing to the spark, explosion and fire.
Related Safety Flashes
-
IMCA SF 20/17
11 August 2017
-
-
IMCA SF 27/20
15 September 2020
-
IMCA SF 12/19
28 May 2019
-
IMCA SF 13/06
21 November 2006
-
IMCA SF 10/11
16 September 2011
IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of the entire offshore industry.
The effectiveness of the IMCA Safety Flash system depends on the industry sharing information and so avoiding repeat incidents. Incidents are classified according to IOGP's Life Saving Rules.
All information is anonymised or sanitised, as appropriate, and warnings for graphic content included where possible.
IMCA makes every effort to ensure both the accuracy and reliability of the information shared, but is not be liable for any guidance and/or recommendation and/or statement herein contained.
The information contained in this document does not fulfil or replace any individual's or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.
Share your safety incidents with IMCA online. Sign-up to receive Safety Flashes straight to your email.