Unintentional selection of manual mode
- DP Event
- Published on 27 February 2018
- Generated on 9 May 2025
- DPE 01/18
- 2 minute read
Incident
Jump to:
The incident highlights the importance of vessel operators risk assessing the DP control station and taking appropriate action as necessary.

Comments
- Initiating event: Inadvertent selection of manual mode whilst in full DP mode.
- Main cause: Human factors – The vessel mode of operation was changed from automatic DP mode to manual DP mode by a double press of the DP manual position button.
- Secondary cause: Computer – No additional barrier (e.g. notification) when manual position selected.
The vessel operator reported that there was an upgrade available to warn the DPO of the change of DP control status and therefore provide additional protection against accidental change of DP control status. The report concluded that all company vessels would be upgraded to include this function.
Considerations
- It is important that DPO training focuses on good practice, an action should be followed up continuously to verify the intention of the action is reached or being executed.
- This type of event has happened on other DP vessels, it is noted that some vessel operators have fitted a cover or made mode of operation buttons stand out from others.
- The incident highlights the importance of vessel operators risk assessing the operation of the DP control station and taking appropriate action as required.
- Consideration should always be given to using joystick auto heading, which can provide tighter control of the vessel, prior to switching to individual manual control of the thrusters.
Latest DP incidents
-
Complete the job
Whilst connected to a turbine, an alarm was generated on the DP operator station, ‘Unbalanced load on SWBD 1’.
DPE 01/25
16 January 2025
Undesired event
-
Beware your centre of rotation
The stern thrusters started to oscillate which transferred to an oscillating motion of the vessel and high forces were being used to try to maintain position.
DPE 01/25
16 January 2025
Incident
-
A-Tension
Whilst pipelaying in shallow water, the vessel experienced a tension sensor failure on one tensioner.
DPE 01/25
16 January 2025
-
How is your alignment?
Loss of the CyScan position reference system generated a reference system failure alarm and moments later the vessel began to lose position with the accompanying alarms.
DPE 01/25
16 January 2025
Incident
-
DP Drill Scenario
DP emergency drill scenarios are included to assist DP vessel management, DPOs / Engineers, and ETOs in conducting DP drills onboard.
DPE 01/25
16 January 2025
Drill Scenario
The case studies and observations above have been compiled from information received by IMCA. All vessel, client, and operational data has been removed from the narrative to ensure anonymity. Case studies are not intended as guidance on the safe conduct of operations, but rather to assist vessel managers, DP operators, and technical crew.
IMCA makes every effort to ensure both the accuracy and reliability of the information, but it is not liable for any guidance and/or recommendation and/or statement herein contained.
Any queries should be directed to DP team at IMCA. Share your DP incidents with IMCA online. Sign-up to receive DP event bulletins straight to your email.